E-STHS: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor can be extended up to 1,000 feet (305 m) via CAT5/5e/6 cable on the E-16D. The cables are sold separately.
[1597]
Comments: 0,
Last Modified: Jan 31, 2018 11:03 AM
- Find Similar
E-STHS: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor can be extended up to 1,000 feet (305 m) via CAT5/5e/6 cable on the E-16D. The cables are sold separately.
[1705]
Comments: 0,
Last Modified: Feb 7, 2018 9:47 AM
- Find Similar
E-STHS: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor can be extended up to 1,000 feet (305 m) via CAT5/5e/6 cable on the E-2D. The cables are sold separately.
[1700]
Comments: 0,
Last Modified: Feb 7, 2018 10:15 AM
- Find Similar
E-STHS: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor can be extended up to 1,000 feet (305 m) via CAT5/5e/6 cable on the E-2D. The cables are sold separately.
[1839]
Comments: 0,
Last Modified: Feb 7, 2018 11:01 AM
- Find Similar
E-STHS: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor can be extended up to 1,000 feet (305 m) via CAT5/5e/6 cable on the E-5D. The cables are sold separately.
[1835]
Comments: 0,
Last Modified: Feb 7, 2018 11:17 AM
- Find Similar
E-STHS: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor can be extended up to 1,000 feet (305 m) via CAT5/5e/6 cable on the E-5D. The cables are sold separately.
[2089]
Comments: 0,
Last Modified: Feb 7, 2018 10:34 AM
- Find Similar
E-TRHM-E7: How far can the combination Temperature/Humidity sensor be extended? The combination Temperature/Humidity sensor is 7 feet (2 m) in length and includes an RJ45 coupler to extend the sensor up to 500 feet (152 m) using CATx cable (minimum 24AWG) from the E-MICRO. The cables are sold separately.
[1593]
Comments: 0,
Last Modified: Jan 31, 2018 10:39 AM
- Find Similar
E-16D: Receive false alerts from the internal humidity sensor Issue: Receive false alerts from the internal humidity sensor every 8 hours to 2 weeks. The alarm email is followed by returned to normal email. Cause: The Sample Period and Alert Delay settings are set too short in the sensor configuration. Solution: Set the Sample period to 10 seconds and the Alert Delay to 30 seconds for the humidity
[2112]
Comments: 0,
Last Modified: Sep 6, 2017 10:23 AM
- Find Similar
power, internal memory (including Log Data) is lost. The IPDU-S4/8 Data Log can be set to preserve itself via automatic messaging under Log > Log Settings > Data Log Settings. To send log entries ... , go to Log > Log Settings > Log To USB Flash Settings and select Enable Log to Flash drive. Logs
[1883]
Comments: 0,
Last Modified: Feb 13, 2024 11:38 AM
- Find Similar
and MIB browser. If they do not, update the MIB browser (see browser configuration) or IPDU settings (under Network Configuration > SNMP Settings) so that the Read-only Community Names and Read ... Read-Write Community Name is “private.” IPDU-Sx SNMP Settings MIB Browser
[2092]
Comments: 0,
Last Modified: Aug 4, 2017 3:27 PM
- Find Similar
. NOTE: If you have a KVM drawer without an integrated switch, you can see if a function is locked on the LED display of the keyboard. If you have a KVM drawer with an integrated switch
[1784]
Comments: 0,
Last Modified: Aug 16, 2013 4:17 PM
- Find Similar
RACKMUX- D15/17 : “No signal” message received Issue: “No signal” error message received. Cause: The input signal is not present immediately after power ON. Solution: Check all cable connections and verify that they are secure. If a multiport switch is attached, ensure a port with active video is selected.