Use the form below to enter your search criteria. By default, all content is searched except for document comments. If you wish to search comments as well as everything else, click "Also Search Comments" below.
[2044]
Comments: 0,
Last Modified: Feb 7, 2018 10:30 AM
- Find Similar
E-MICRO-TRHP: Receive false alerts from the integrated humidity sensor Issue: Receive false alerts from the integrated humidity sensor every 8 hours to 2 weeks. The alarm email is followed by returned to normal email. Cause: The Sample Period and Alert Delay settings are set too short in the sensor configuration. Solution: Set the Sample period to 10 seconds and the Alert Delay to 30
[2105]
Comments: 0,
Last Modified: Feb 7, 2018 10:33 AM
- Find Similar
E-MICRO: Does the Included Power Supply Adjust for Input Voltage? Yes. The power supply included with the E-MICRO is a switching power supply. It will automatically sense and adjust for input voltage, provided the voltage is within the acceptable range of 100 to 240 VAC at 50 or 60 Hz.
[2088]
Comments: 0,
Last Modified: Feb 7, 2018 10:34 AM
- Find Similar
E-MICRO: How Many E-MICRO Units can be Connected to an E-xD Master/Slave Cascade Configuration When configuring an advanced Master and Slave cascade, a maximum of eight E-MICRO IP Sensors can be connected to the configuration. This is because IP Sensor configuration can only be done through the E-xD Master unit, which allows for up to eight connected IP Sensors. NOTE: Sensors connected
[2078]
Comments: 0,
Last Modified: Feb 13, 2024 11:54 AM
- Find Similar
’ email address in the E-MICRO web server under Administration > Users > Contact Settings ... Settings” and/or “Critical Alert Settings” > Enable Email Alerts.
[1566]
Comments: 0,
Last Modified: Feb 7, 2018 10:44 AM
- Find Similar
computer and E-MINI-LXO are in same subnet. Log into unit via USB console. Configure “Network Settings” to ensure that both computer and unit are in the same subnet.
[1568]
Comments: 0,
Last Modified: Feb 7, 2018 10:43 AM
- Find Similar
“root” password is remembered, restore default settings by taking the following steps (WARNING: will erase ALL user configuration settings, including IP address and login information). Access the ENVIROMUX through a terminal program via the USB console. Select “System Configuration” under the Main Menu. Select “Restore Settings to Defaults&rdquo
[2101]
Comments: 0,
Last Modified: Feb 7, 2018 10:46 AM
- Find Similar
Normal 0 false false false EN-US X-NONE X-NONE E-MINI-LXO: Does the Included Power Supply Adjust for Input Voltage? Yes. The power supply included with the E-MINI-LXO is a switching power supply. It will automatically
[2111]
Comments: 0,
Last Modified: Feb 7, 2018 10:45 AM
- Find Similar
E-MINI-LXO: How To Preserve the Event and Data Logs When an E-MINI-LXO loses power, internal memory (including Log Data) is lost. The E-MINI-LXO Data Log can be set to preserve itself via automatic messaging under Log > Log Settings > Data Log Settings. To send log entries, enable ... drive, go to Log > Log Settings > Log To USB Flash Settings and select Enable Log to Flash
[1918]
Comments: 0,
Last Modified: Feb 7, 2018 10:47 AM
- Find Similar
E-MINI-LXO: How to Turn Off Public SNMP SNMP public access is part of SNMP v1 and v2c. To disable these versions, take the following actions: On the web interface, go to Administration > Network > SNMP settings. Under “Enable SNMP Agent” select “SNMPv3” in the drop down menu and then select save on the bottom of the screen.
335 results for: