E-MINI-LXO: "Out of Sensor Range" error message when changing temperature readings from Celsius to Fahrenheit.
Issue: "Out of Sensor Range" error message when changing temperature readings from Celsius to Fahrenheit.
Cause: The E-MINI-LXO only reads values as Fahrenheit after the change has been saved. When the numbers are automatically converted into Fahrenheit, the unit is still reading them in Celsius until the change is saved.
Solution: When changing temperature reading unit from Celsius to Fahrenheit, write down the converted Fahrenheit values on a piece of paper. Adjust the input values on the screen to range between -20 and 70. Save the configuration as Fahrenheit—there should be no error message. Key in the previously recorded values and hit "save" again.