Gas Detection Sensors compatible with E-2D, E-5D and E-16D
Gas Detection Sensors
Carbon Monoxide (CO) Detector
E-CMD
Continuous air monitoring.
Pre-set alarm points alert at:
70 ppm after 60 to 240 minutes
150 ppm after 10 to 50 minutes
400 ppm after 4 to 15 minutes
Flush or surface mount.
Test functionality of electrochemical CO sensing cell.
Connect to RJ45 or digital input sensor ports.
Screw terminal
To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-terminated end to the sensor screw terminal.
Maximum cable length: 1000 ft (305m)
LED indicators for operation status and system test.
Operating relative humidity: 15 to 90% non-condensing RH.
Requires the E-S5VDC sensor converter to operate with E-2D/5D/16D.
E-S5VDC maximum cable length: 1000 ft (305 m).
E-S5VDC powered by E-2D/5D/16D.
0 to 5 VDC output.
Powered by E-S5VDC sensor converter.
Current consumption: 20mA @ 12VDC.
Regulatory approvals: CE
Hydrogen Sulfide Detector
E-H2S
Use to monitor the presence of Hydrogen Sulfide from failed UPS (uninterrupted power supply) lead acid batteries, in paper mills, refineries, waste disposable facilities, etc.
Measures H2S in a range of 0 to 50 ppm.
5A SPDT fan relay controls exhaust fans, valves, or louvers.
Alerts are based solely on the measured H2S levels reported by the E-H2S.